Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Generator testing has not yet been tested and shall be tested to complete the inspection 7/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone in the elevator does not work on 110v emergency power or normal power. Repair or replace. If violation is not corrected in 14 days the elevator will be locked out of service. 5/25/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The elevator pit shall be cleaned of dust and debris.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) The car door “open” button failed to operate on the car operating panel opposite of the Fireman’s Service phase II cabinet.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety. Reinspection required. 5/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The elevator pit shall be cleaned of dust and debris.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Elevator pit shall be clean of dust and debris
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone in the elevator does not work on 110v emergency power or normal power. Repair or replace 7/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in elevator machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Current maintenance records shall be kept in the elevator machine room
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform 125% brake test and unintended movement test. Re-inspection required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work, speaker works, microphone does not. Re-inspection required