Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Generator testing has not yet been tested and shall be tested to complete the inspection 7/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The elevator pit shall be cleaned of dust and debris. 6/24/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The elevator pit shall be cleaned of dust and debris. 6/24/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. 6/24/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. 6/24/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. 6/24/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform 125% brake test and unintended movement test. Re-inspection required 5/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written copy of the MCP shall be kept in the machine room for each unit 6/24/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room 6/24/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Need to test elevator on phase I & II. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 Need to clean trash from the pit 6/24/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to perform the following tests to complete inspection: Test elevator for operation on emergency power, perform unintended car movement test with no load in car, perform 125% brake test and unintended movement test with 125% of rated load. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room 6/24/2025