MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete due to roller broke on sling. Need to perform the following tests to complete inspection: Test safeties, phone, emergency lights & bell, OSV, cartop, & door restrictor. Re-inspection required
|
3/31/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Inspection incomplete. The OSV still needs to be tested. The elevator quit running during inspection
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.13.1
|
x
|
|
Install floor covering and handrail in elevator cab.
|
7/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.13.3.4
|
x
|
x
|
Install smoke detectors for fire recall and program.
|
7/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.26.2.7
|
x
|
|
Install single 110v receptacle in pit for sump pump.
|
7/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Install shunt trip disconnect in the elevator machine room.
|
7/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
x
|
|
Install car buffers or bumpers.
|
7/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.3
|
x
|
|
Install fire rated door on the elevator machine room.
|
7/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
x
|
|
Change receptacles in machine room to GFIC
|
7/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
8/26/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide phone line for emergency two-way communication.
|
7/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Install fire extinguisher in elevator machine room.
|
7/12/2019
|