Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.13.3.4 x x Fire alarm device at top of hoistway shall hold the car at top floor at activation. Did not red tag. 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19.4.1 x A manually operated shutoff valve shall be provided between the hydraulic machines and the hydraulic jack and shall be located outside the hoistway and adjacent to the hydraulic machine. 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.4 x A manually operated valve shall be located on or adjacent to the control valve. 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.5 x A pressure switch shall be provided in the line between the cylinder and the valve, which shall be activated by the loss of positive pressure at the top of the cylinder. 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Control space required to be illuminated to 19 ft candles measured at the car top in front of the controller
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting Illumination in machine room is less than 19 fc on cartop at control space. Need to install proper lighting in hoistway
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting Illumination in machine room is less than 19 fc on cartop at control space. Need to install proper lighting in hoistway