ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19.4.1
|
x
|
|
A manually operated shutoff valve shall be provided between the hydraulic machines and the hydraulic jack and shall be located outside the hoistway and adjacent to the hydraulic machine.
|
9/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.4
|
x
|
|
A manually operated valve shall be located on or adjacent to the control valve.
|
9/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.5
|
x
|
|
A pressure switch shall be provided in the line between the cylinder and the valve, which shall be activated by the loss of positive pressure at the top of the cylinder.
|
9/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
Control space required to be illuminated to 19 ft candles measured at the car top in front of the controller
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.13.3.4
|
x
|
x
|
Fire alarm device at top of hoistway shall hold the car at top floor at activation. Did not red tag.
|
9/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Illumination in machine room is less than 19 fc on cartop at control space. Need to install proper lighting in hoistway
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Illumination in machine room is less than 19 fc on cartop at control space. Need to install proper lighting in hoistway
|
|