Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x All phases of fire service shall be tested. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Check for proper operation of the emergency phone. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) x Check hoistway access. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency power operation of the elevators shall be tested. 4/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) x Finish construction of the elevator lobby and mount all fixtures and signage. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) x Finish grouting the sills. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) x Finish the elevator floor. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x Finish the installation of the sump pump and cover. 5/11/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Install a ABC Rated Fire Extinguisher on the 5th floor in sight of the elevator controls 3/18/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Install ABC Rated extinguisher on 5th floor in view of controller 9/21/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) x Install all electrical covers. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits x Install lighting (10 ftc) in the pit with switch and GFCI. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) x Install lighting (19 ftc) in overhead machine space with switch and GFCI. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.11 Install Missing fire stops on hoistway doors 9/21/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 x Label disconnects for feed source. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 x Number the hoistway doors. 5/11/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room 3/18/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Perform monthly fire service test and document on log in machine room 9/21/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Remove prints and maintenance records from top of car 9/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Remove storage from the top of the car 6/26/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) x Seal all penetrations in the hoistway. 5/11/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency power operation 3/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.3.2 x The counterweight guard must extend from the lowest part of the counterweight assembly when the counterweight is resting on the fully compressed buffer. 5/18/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency lighting and alarm shall be tested. 5/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x The emergency power indicator light shall illuminate to indicate the standby/emergency power is activated. The indicator light shall be operational and emergency power shall be tested. 6/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone is still not operational. 6/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 4/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.11 - Hoistway smoke control 2.1.4 The powered hoistway vent in the overhead shall automatically open upon detection of smoke in the elevator lobbies or hoistway, and upon power failure. 5/18/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 The powered hoistway vent in the overhead shall be sealed with masonry or other approved solid materials. 5/18/2020