Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Door restrictor inoperable, repair in 15 days. Re-inspection required 8/11/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x Car door restrictor still does not work, parts missing. Re-inspection required 8/11/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x Car door restrictor is not working. Re-inspection required 2/6/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 x Increase illumination to 19 ft candles 7/31/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be provided on site for each elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Close hoistway penetration 7/31/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 2.1.5 x Grout floor sills 7/31/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x Pit lights are inoperative. 7/31/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.26.2.7 x Cover pit sump even with pit floor. 7/31/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.13.3.4 x x Reprogram basement, 3rd & 4th floor smoke detectors to recall to primary floor. 7/31/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.13.3.4 x x Reprogram top of hoistway smoke detector to recall to primary floor and flash the hat. 7/31/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.13.5 x x Reprogram the top of hoistway heat detector to trip the shunt. 7/31/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Post Phase I instructions near f/f switch in lobby.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.