MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
x
|
|
Provide code compliant pit lighting, currently measured at 3.9fc.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
x
|
|
Provide pit floor to be flush to prevent tripping hazard.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.8 - Hoistway enclosure
|
8.11.2.1.4(h)
|
x
|
|
1st floor (lobby floor front) floor is not flush and creates a potential tripping hazard.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
8.11.2.1.3(o)
|
x
|
|
Provide numbering of the car top.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
8.11.2.1.3(s)
|
x
|
|
Top of hoistway has ledge exceeding 4". Provide means to remove this condition.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
8.11.2.1.3(s)
|
x
|
|
Remove all screws projecting into hoistway walls.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
x
|
|
Seal all penetrations in the hoistway.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
x
|
|
Provide a current tested fire extinguisher in the elevator machine room.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
x
|
|
Clean the machine room.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
8.11.2.1.2(d)
|
x
|
|
Seal all penetrations in the machine room.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
x
|
|
Provide code compliant machine room lighting, currently measured at 3.8fc.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Provide feeder location on main line and 110v disconnect.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Provide testing of emergency battery back up system.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
8.11.2.1.2(j)
|
x
|
|
Provide numbering in the machine room, i.e. controller, main line disconnect, etc.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
x
|
|
Provide machine room door to be UL listed.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
x
|
|
The machine room door shall be self-closing and self-locking.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall work with 24/7 support.
|
12/23/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone was not answered, phone must be answered 24/7. Re-inspection required
|
6/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in control room is expired, replace or have serviced
|
|