Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 x Provide feeder location on main line and 110v disconnect. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) x Provide numbering of the car top. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) x Provide numbering in the machine room, i.e. controller, main line disconnect, etc. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) x Provide machine room door to be UL listed. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) x The machine room door shall be self-closing and self-locking. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) x Provide code compliant machine room lighting, currently measured at 3.8fc. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) x Provide a current tested fire extinguisher in the elevator machine room. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 8.11.2.1.2(d) x Seal all penetrations in the machine room. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 x Provide testing of emergency battery back up system. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) x Clean the machine room. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) x 1st floor (lobby floor front) floor is not flush and creates a potential tripping hazard. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 8.11.2.1.3(s) x Top of hoistway has ledge exceeding 4". Provide means to remove this condition. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 8.11.2.1.3(s) x Remove all screws projecting into hoistway walls. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) x Seal all penetrations in the hoistway. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall work with 24/7 support. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits x Provide code compliant pit lighting, currently measured at 3.9fc. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits x Provide pit floor to be flush to prevent tripping hazard. 12/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone was not answered, phone must be answered 24/7. Re-inspection required 6/5/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in control room is expired, replace or have serviced