Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Fire service operation, smokes, heats, powered hoistway venting, and other associated items must be completed and tested. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting Yes No The emergency lighting shall be operational. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The alarm bell shall operate on auxiliary power. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) Yes No The elevator floor and lobby floors must be finished and landings sills grouted. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Yes No Permanent main line and lighting power shall be provided and shall have feeder locations marked. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Yes No The penetrations in the hoistway shall be sealed with approved solid material. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Yes No A written maintenance control program (MCP) shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No All electrical device and wireway covers shall be installed. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No A light switch, lighting, and GFCI receptacle must be installed in the overhead. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 Yes No A light switch, light, and GFCI receptacle must be installed in the pit. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Yes No A fire extinguisher must be provided and mounted convenient to the top landing hall door. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided Yes No Installation of the pit sump pump must be completed and the cover must be installed. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes The building fire control station must be installed and tested. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 Seismic (Earthquake protection) 8.4.10 Yes No The counterweight displacement system must be installed and tested. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 No No Hoistway door bottom retainers required 7/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) No No Install wiring cover on hoist machine. Violation code 2.8.1 7/19/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete, need to test Emergency power. Re-inspection required 1/9/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Yes No EP/Lobby panel has key switches and jewels that indicate car #4 has EP. Per Kone, #4 is not on EP; remove switches and jewels for #4 that are not appropriate for the current configuration. 7/23/2026