ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Install fire extinguisher in machine space.
|
5/1/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.1.4(l)
|
x
|
x
|
Install smoke detector within 24" of sprinkler heads at top of hoistway to activate shunt trips. DID NOT RED TAG
|
5/1/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
Secure hoistway venting damper to frame and seal end of beam.
|
5/1/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5 year testing incomplete. Must perform the following to complete test. Set safeties, 125% brake test, pull out and pull through and spinning the governor
|
11/15/2024
|