Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x 5 year testing incomplete. Must perform the following to complete test. Set safeties, 125% brake test, pull out and pull through and spinning the governor 11/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Install fire extinguisher in machine space. 5/1/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) x x Install smoke detector within 24" of sprinkler heads at top of hoistway to activate shunt trips. DID NOT RED TAG 5/1/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Secure hoistway venting damper to frame and seal end of beam. 5/1/2019