Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Cat 5 test incomplete, need to perform the following tests to complete inspection: pit devices, car slide (safeties have been set), governor pull out and pull through, governor speeds, door pressure & fire service. Re-inspection required 1/30/2024