Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.12 x Plunger on governor switch is broken. Switch functions, but cannot be reset with without disassembling of switch, need to replace switch. Re-inspection required 10/1/2024
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.12 x Governor remote trip / reset function does not work, needs repaired. Re-inspection required 10/1/2024
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.12 x Governor remote trip / reset function does not work, needs repaired. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 x Government remote trip / reset function does not work, needs repaired. Re-inspection required 11/29/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 2.26.2.22 x Gas spring return buffers shall be equipped with a switch to disconnect power to the driving machine in the event that a buffer is not within an 1/2 inch of its fully extended position. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.26.2 x Plunger on governor switch is broken. Switch functions, but cannot be reset without disassembling of switch, replace switch. Re-inspection required 11/29/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone in car is not working. Re-inspection required 12/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Light in pit is not working, needs repair 8/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x Sump pump in pit is not working, needs repair. Re-inspection required 12/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Pit light is not working, needs repair 8/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x Sump pump in pit is not working, needs repair. Re-inspection required 10/20/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x Final limit switch does not work in the down direction, needs repaired. Red-tagged, Re-inspection required 11/29/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Compensation rope displacement switch on bottom of elevator cab appears to have water damage and could not be reset, replace switch. Re-inspection required 11/29/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Compensation rope displacement switch on bottom of elevator cab appears to have water damage and could not be reset, replace switch. Re-inspection required 10/1/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Governor rope is below minimum diameter and shall be replaced. Re-inspection required