ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
Pit light is not working, needs repair
|
8/23/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
Light in pit is not working, needs repair
|
8/23/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump pump shall be provided
|
x
|
|
Sump pump in pit is not working, needs repair. Re-inspection required
|
12/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car is not working. Re-inspection required
|
12/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump pump shall be provided
|
x
|
|
Sump pump in pit is not working, needs repair. Re-inspection required
|
10/20/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
x
|
Final limit switch does not work in the down direction, needs repaired. Red-tagged, Re-inspection required
|
11/29/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.26.2
|
x
|
|
Plunger on governor switch is broken. Switch functions, but cannot be reset without disassembling of switch, replace switch. Re-inspection required
|
11/29/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Compensation rope displacement switch on bottom of elevator cab appears to have water damage and could not be reset, replace switch. Re-inspection required
|
11/29/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.18
|
x
|
|
Government remote trip / reset function does not work, needs repaired. Re-inspection required
|
11/29/2023
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.12
|
x
|
|
Plunger on governor switch is broken. Switch functions, but cannot be reset with without disassembling of switch, need to replace switch. Re-inspection required
|
10/1/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Compensation rope displacement switch on bottom of elevator cab appears to have water damage and could not be reset, replace switch. Re-inspection required
|
10/1/2024
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.12
|
x
|
|
Governor remote trip / reset function does not work, needs repaired. Re-inspection required
|
10/1/2024
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.12
|
x
|
|
Governor remote trip / reset function does not work, needs repaired. Re-inspection required
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Governor rope is below minimum diameter and shall be replaced. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
2.26.2.22
|
x
|
|
Gas spring return buffers shall be equipped with a switch to disconnect power to the driving machine in the event that a buffer is not within an 1/2 inch of its fully extended position. Re-inspection required
|
|