Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) Post Phase I instructions near f/f switch in the lobby..
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Numerous buttons stuck/ sticking, replace as needed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power.
A17.1-2016 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide testing of the elevator emergency power selector switch (fire control room).
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide existing alarm bell to work (both C O Ps).
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide 125% brake test.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Car handrails ( both) missing, provide.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Unable to locate room with disconnect. Locate and test emergency lights and bell.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) Post Phase I instructions in lobby, near f/f switch.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair stuck door open and close buttons in front and rear car stations
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Seal hoistway penetrations. 10/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Add second higher rated heat detector for shunt trip on 7th floor. 10/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 x Provide 19 foot candles at the 7th floor control space. 10/16/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Perform the annual emergency power operation testing on the elevators 12/11/2024