Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x All elevators are required to be tested under emergency power. 11/20/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x All elevators are required to be tested under emergency generator annually. Re-inspection required 1/28/2025
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.20.1 x Need to test car safeties at rated speed with rated load. Re-inspection required 2/7/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Need to test elevator for operation on emergency power. Re-inspection required 2/7/2025
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.20.1 x Need to test car safeties at rated speed with rated load. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) x Fill all holes and voids in hoistway. 12/5/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Provide fire extinguisher in machine space. 12/5/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 12/5/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Smokes and heats shall work. 12/5/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair stuck front and rear in car door operation buttons
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Need to repair stuck and damaged door open and door close buttons
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair stuck front & rear door operation buttons
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Need to repair stuck and damaged door open and door close buttons