Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods There is no fed from information in the controller to show where the main line power is fed from
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 There is no code data tag with information that shows what code the elevator is inspected to
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone needs to be reprogrammed 9/29/2022
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.11.3.1.2(m) Main disconnect in Electrical equipment room (1st Floor) needs to be labeled in controller and on that disconnect the location. 7/12/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) Need buckets in pit for oil collection from cylinder heads 7/12/2023
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Overspeed valve not sealed. Due full load test next year 7/12/2023