MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
There is no fed from information in the controller to show where the main line power is fed from
|
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
There is no code data tag with information that shows what code the elevator is inspected to
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone needs to be reprogrammed
|
9/29/2022
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
8.11.3.1.2(m)
|
|
|
Main disconnect in Electrical equipment room (1st Floor) needs to be labeled in controller and on that disconnect the location.
|
7/12/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
Need buckets in pit for oil collection from cylinder heads
|
7/12/2023
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Overspeed valve not sealed. Due full load test next year
|
7/12/2023
|