Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records Documents on top of the car. Relocate to machine room 9/22/2021
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 Provide feeder location for mainline disconnect and 110v disconnect. Both in top of hoistway 9/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Need to perform unintended movement test. Re-inspection required 11/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Need to provide specific documentation for tests & inspections for MCP
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is not working, repair or replace. Reprogram phone to call current elevator maintenance company or a 24 hr security service. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Hoistway vent not wired. 8/29/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Seal hoistway penetrations. 8/29/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, no weights for Cat 5 test. Need to complete the following tests: 125% brake test, full load safeties, unintended motion up & down. Re-inspection required