MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete, no weights for Cat 5 test. Need to complete the following tests: 125% brake test, full load safeties, unintended motion up & down. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Seal hoistway penetrations.
|
8/29/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
Hoistway vent not wired.
|
8/29/2019
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
|
|
Provide feeder location for mainline disconnect and 110v disconnect. Both in top of hoistway
|
9/22/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working, repair or replace. Reprogram phone to call current elevator maintenance company or a 24 hr security service. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Need to perform unintended movement test. Re-inspection required
|
11/27/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Need to provide specific documentation for tests & inspections for MCP
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
Documents on top of the car. Relocate to machine room
|
9/22/2021
|