Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Re-inspection required
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5c Receptacles Yes No Receptacles in the elevator machine room shall be GFCI 8/21/2019
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Yes No Remove auxiliary sump pump alarm from the machine room. 8/21/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 Yes No Remove the sump pump controller from the elevator pit. 8/21/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Yes No Increase sump pump capacity to 3000 gpm 8/21/2019