MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
x
|
|
Increase sump pump capacity to 3000 gpm
|
8/21/2019
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5c Receptacles
|
x
|
|
Receptacles in the elevator machine room shall be GFCI
|
8/21/2019
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
x
|
|
Remove auxiliary sump pump alarm from the machine room.
|
8/21/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
102
|
x
|
|
Remove the sump pump controller from the elevator pit.
|
8/21/2019
|