Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be on display in the machine room 5/6/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be on display in the machine room 5/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 No No The machine room door shall be self-closing, self-locking, and operable from the interior space without the use of a key. 5/6/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency two way communication is inoperable. The phone shall be able to establish two communication. Repair or replace 6/13/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall work, appears not to have a live phone line. Re-inspection required 5/9/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2-way communication device shall work with and without main power and give proper location. 6/18/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency two way communication is inoperable. The phone shall be able to establish two communication. Repair or replace 5/6/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency two way communication is inoperable. The phone shall be able to establish two communication. Repair or replace
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 8/22/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 Yes No Emergency battery lowering unit does not work. Repair or replace. REINSPECT IN 14 DAYS
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 Yes No Emergency battery lowering unit does not work. Repair or replace. REINSPECT IN 14 DAYS 5/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) Yes No Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. 6/18/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 Yes No Emergency battery lowering unit does not work. Repair or replace. REINSPECT IN 14 DAYS 6/13/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room door shall be self-closing, self-locking, and operable from the interior space without the use of a key. 5/6/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, have serviced or replaced 5/6/2026