Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.11 - Hoistway smoke control 2.1.4 x hoistway damper not working 7/1/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.11 - Hoistway smoke control 2.1.4 x !st floor smoke screen not working on No.1 Elev in Joint hoistway will need temp insp use insp. to use no1 till smokescreen repaired. 7/1/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Smoke curtain on Elev 1, which shares joint hoistway with this elevator, does not operate on bottom level 7/1/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices x x alarm int.device not working 7/1/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room 11/11/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 2/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 1/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.22 - Wire rope fastening and hitch plate 8.11.2.1.3(bb) x Adjust wedge shackle retainer clips for proper spacing. 12/8/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) MRL not up to date 2/1/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test operation of elevator on emergency power 12/8/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test elevator operation on emergency power 10/23/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency power was not tested. 11/13/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency power operation 12/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Remove gallon containers of oil, and wooden posts from pit floor. 11/11/2023