ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
!st floor smoke screen not working on No.1 Elev in Joint hoistway will need temp insp use insp. to use no1 till smokescreen repaired.
|
7/1/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
8.11.2.1.3(bb)
|
x
|
|
Adjust wedge shackle retainer clips for proper spacing.
|
12/8/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices
|
x
|
x
|
alarm int.device not working
|
7/1/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
hoistway damper not working
|
7/1/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
MRL not up to date
|
2/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room
|
11/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove gallon containers of oil, and wooden posts from pit floor.
|
11/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
Smoke curtain on Elev 1, which shares joint hoistway with this elevator, does not operate on bottom level
|
7/1/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
2/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
1/5/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test elevator operation on emergency power
|
10/23/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test emergency power operation
|
12/13/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test operation of elevator on emergency power
|
12/8/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
The emergency power was not tested.
|
11/13/2024
|