Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Abate black mold in pit. 9/29/2022
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) Yes No Emergency light is inoperable. Re-inspection required
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 5/12/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit has ground water entering, waterproof as needed. 9/29/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit needs to be clean of water and debris. 5/3/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current certificate. 9/29/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) No No Post Phase I instructions in lobby, near f/f switch. 9/29/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing of the elevator is incomplete. The unit shut down in middle of inspection. The following things need to be tested to complete the annual: set the safeties, unintended motion up, 110v emergency power, the pit items, and fire service. The other car was not inspected at this time. 3/25/2026