Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 Clean floor----oil 4/12/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 Clean floor and pan under hydro unit 3/2/2023
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.10.3.2.2(s) x 8.7.2.8 - Electrical clearance on newly installed controller for Major Alteration is not met. Current clearance is 0" per NFPA 70. 2/6/2025
conversion conversion n/a Car floor tile cracked,chipped-missing- tripping hazzard 8/3/2018