ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
x
|
|
Finish the installation of the hall walls and install all signage.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
8.11.2.1.1(d)
|
x
|
|
Finish the installation of the cab flooring.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
8.11.2.1.1(d)
|
x
|
|
Grout all sills
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.3 Provide Auxiliary Lighting
|
x
|
|
Emergency lighting shall be tested.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone and alarm shall be tested.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
2.29.1
|
|
|
label controller & car sling
|
5/24/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
8.6.1.6.3
|
|
|
Remove prints and maintenance control program from the top of the car & provide a secure container outside the hoistway
|
5/24/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.18
|
x
|
|
Test tags shall be installed on the governor.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.29 - Car and counterweight safeties
|
2.17
|
x
|
x
|
The safety slide is too short. It should be between 10" and 40"
|
10/15/2020
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
Provide a ABC rated fire extinguisher within sight of controller on the 7th floor
|
5/24/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
x
|
|
All electrical covers shall be installed.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Seal all penetrations in the hoistway.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
|
|
The powered smoke control vent in the overhead shall automatically open upon detection of smoke in the elevator lobbies or hoistway, upon power failure, and upon activation of a manual override control.
|
10/15/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
x
|
|
Finish installing light, switch, and GFI in overhead.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
2.20
|
x
|
|
Test tags shall be installed on hoist cables.
|
10/14/2020
|
A17.1-2016 : Elevators
|
4.4 - Hoistway door locking devices
|
8.11.2.1.4(d)
|
x
|
|
Install fire stops on all hoistway doors
|
5/2/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
x
|
|
Finish installing light, switch, and GFI in pit.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump pump shall be provided
|
x
|
|
Finish the installation of the sump pump in the pit.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
8.11.2.1.5(c)
|
x
|
|
Test tags shall be installed on the buffers.
|
10/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
All phases of fire service shall be tested.
|
10/14/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Perform monthly fire service and document on log in machine room
|
5/24/2022
|