Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.4 - Hoistway door locking devices 8.11.2.1.4(d) x Install fire stops on all hoistway doors 5/2/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) Provide a ABC rated fire extinguisher within sight of controller on the 7th floor 5/24/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Perform monthly fire service and document on log in machine room 5/24/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.6.1.6.3 Remove prints and maintenance control program from the top of the car & provide a secure container outside the hoistway 5/24/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 label controller & car sling 5/24/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) x Finish installing light, switch, and GFI in overhead. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits x Finish installing light, switch, and GFI in pit. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x Finish the installation of the sump pump in the pit. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Seal all penetrations in the hoistway. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) x Finish the installation of the hall walls and install all signage. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x All phases of fire service shall be tested. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone and alarm shall be tested. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting x Emergency lighting shall be tested. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) x All electrical covers shall be installed. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 x Test tags shall be installed on hoist cables. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) x Finish the installation of the cab flooring. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) x Grout all sills 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 x Test tags shall be installed on the governor. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.11.2.1.5(c) x Test tags shall be installed on the buffers. 10/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.29 - Car and counterweight safeties 2.17 x x The safety slide is too short. It should be between 10" and 40" 10/15/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.11 - Hoistway smoke control 2.1.4 The powered smoke control vent in the overhead shall automatically open upon detection of smoke in the elevator lobbies or hoistway, upon power failure, and upon activation of a manual override control. 10/15/2020