Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Seal hoistway penetrations. 7/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x Phase II door close is not functioning because controller is not seeing key in on position. Re-inspection required 7/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Testing incomplete - need to test fire service & emergency light, bell & phone. Re-inspection required 6/26/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 7/16/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator on emergency power. 1/8/2025
A17.1-2016 : Elevators 4.12 - Standby power selection switch 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator emergency power selector switch. 1/8/2025