Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No This elevator has a backup emergency generator power that is used in case of a power outage. This system was setup and scheduled to be tested on 10/26/24, however the hospital staff failed to initiate the emergency generator test. Reinspection is required. 10/30/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 11/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No Incomplete inspection - check fire service and standby power upon return. 11/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No Need to perform testing of emergency generator power operation and fire service. Re-inspection required 10/1/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to perform emergency generator power operation testing, fire service testing. Re-inspection required 9/30/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Emergency Generator Power, Fire Service operation, and Hospital Service operation shall be tested
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 Yes No Governor - Remote SET/RESET functions shall work as designed. Will not fully perform remote Reset, crew had to manually reset from the cartop(no access door) Unit is designed to remote set and remote reset.
A17.1-2016 : Elevators 2.27 - Rope fastenings 8.6.2.5 Yes No Ropes showing signs of rouge and several areas of fraying. Replace ropes within 30 days. Reinspection required. 2/11/2026
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) Yes No Hoist ropes are rouged and have sufficient breaks to warrant replacement. Replace same. Re-inspection required 1/5/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) Yes No Hoist ropes are rouging and have sufficient breaks to warrant replacement., replace same within 90 days. Re-inspection required 10/1/2022
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 2.20.2 No No Replace incorrect crosshead date plate and missing hoist rope data tag 11/5/2021