A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system was setup and scheduled to be tested on 10/26/24, however the hospital staff failed to initiate the emergency generator test. Reinspection is required.
|
10/30/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone does not work.
|
11/21/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
Yes
|
No
|
Incomplete inspection - check fire service and standby power upon return.
|
11/21/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
Yes
|
No
|
Need to perform testing of emergency generator power operation and fire service. Re-inspection required
|
10/1/2022
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Need to perform emergency generator power operation testing, fire service testing. Re-inspection required
|
9/30/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Emergency Generator Power, Fire Service operation, and Hospital Service operation shall be tested
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.18
|
Yes
|
No
|
Governor - Remote SET/RESET functions shall work as designed. Will not fully perform remote Reset, crew had to manually reset from the cartop(no access door) Unit is designed to remote set and remote reset.
|
|
|
A17.1-2016 : Elevators
|
2.27 - Rope fastenings
|
8.6.2.5
|
Yes
|
No
|
Ropes showing signs of rouge and several areas of fraying. Replace ropes within 30 days. Reinspection required.
|
2/11/2026
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
Yes
|
No
|
Hoist ropes are rouged and have sufficient breaks to warrant replacement. Replace same. Re-inspection required
|
1/5/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
Yes
|
No
|
Hoist ropes are rouging and have sufficient breaks to warrant replacement., replace same within 90 days. Re-inspection required
|
10/1/2022
|
|
A17.1-2016 : Elevators
|
3.27 - Crosshead Data Plate and Rope Data Tags
|
2.20.2
|
No
|
No
|
Replace incorrect crosshead date plate and missing hoist rope data tag
|
11/5/2021
|