MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform emergency generator power operation testing, fire service testing. Re-inspection required
|
9/30/2023
|
A17.1-2016 : Elevators
|
3.27 - Crosshead Data Plate and Rope Data Tags
|
2.20.2
|
|
|
Replace incorrect crosshead date plate and missing hoist rope data tag
|
11/5/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Need to perform testing of emergency generator power operation and fire service. Re-inspection required
|
10/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Incomplete inspection - check fire service and standby power upon return.
|
11/21/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
11/21/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
x
|
|
Hoist ropes are rouging and have sufficient breaks to warrant replacement., replace same within 90 days. Re-inspection required
|
10/1/2022
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
Hoist ropes are rouged and have sufficient breaks to warrant replacement. Replace same. Re-inspection required
|
1/5/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system was setup and scheduled to be tested on 10/26/24, however the hospital staff failed to initiate the emergency generator test. Reinspection is required.
|
10/30/2024
|