Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform emergency generator power operation testing, fire service testing. Re-inspection required 9/30/2023
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 2.20.2 Replace incorrect crosshead date plate and missing hoist rope data tag 11/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Need to perform testing of emergency generator power operation and fire service. Re-inspection required 10/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Incomplete inspection - check fire service and standby power upon return. 11/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 11/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) x Hoist ropes are rouging and have sufficient breaks to warrant replacement., replace same within 90 days. Re-inspection required 10/1/2022
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x Hoist ropes are rouged and have sufficient breaks to warrant replacement. Replace same. Re-inspection required 1/5/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system was setup and scheduled to be tested on 10/26/24, however the hospital staff failed to initiate the emergency generator test. Reinspection is required. 10/30/2024