Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform testing of emergency generator power operation & fire service testing. Re-inspection required 9/30/2023
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 2.20.2 Replace missing crosshead date plate and incorrect hoist rope date tag 11/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Need to perform testing of emergency generator power operation and fire service. Re-inspection required 10/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Incomplete annual inspection - test standby power and fire service upon return. 11/22/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.28 - Terminal stopping devices 8.11.2.1.2(z) x x Up normal limit not working, repair and reinspect. Did not red tag unit. 11/22/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system was setup and scheduled to be tested on 10/26/24, however the hospital staff failed to initiate the emergency generator test. Reinspection is required. 10/30/2024