Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.27 - Crosshead data plate 8.11.2.1.3(k) Crosshead shall be identified with minimum 2" numbers. 11/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Incomplete test - upon return test standby power and fire service. 11/21/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform testing of emergency generator power operation & fire service testing. Re-inspection required 9/30/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Need to perform testing of emergency power generator operation and fire service. Re-inspection required 10/1/2022
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 2.20.2 Replace incorrect crosshead data plate and missing hoist rope data tag 11/5/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system was setup and scheduled to be tested on 10/26/24, however the hospital staff failed to initiate the emergency generator test. Reinspection is required. 10/30/2024