ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Standing water in the pit, clean and address source of water, may need to dig out trench to drain water into sump pit
|
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
|
|
all sheetrock screws projecting into the hoistway need to be cut off flush to the wall
|
9/30/2021
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
2.12.7
|
|
|
the top landing hoistway access down limit has not been set up
|
9/30/2021
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
2.12.7
|
|
|
The bottom landing hoistway access up limit has not been set up
|
9/30/2021
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
need to post a copy of the state operating certificate in the machine room
|
9/30/2021
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
monthly fire service test log is to be posted in the machine room
|
9/30/2021
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
clean the pit, oil on pit floor
|
3/27/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, provide working phone line
|
4/2/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. (8.6.4.8.2)
|
4/2/2024
|