Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.5 - Access to Hoistway 2.12.7 top landing hoistway access did not work at all 9/30/2021
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 all sheetrock screws projecting into the hoistway need to be cut off flush to the wall 9/30/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a copy of the state operating certificate needs to be posted in the machine room 9/30/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Fire service test log is to be posted in the machine room 9/30/2021
A17.1-2016 : Elevators 4.5 - Access to Hoistway 2.12.7 bottom landing hoistway access ran the elevator up and then the elevator shutdown, repair hoistway access so it works 9/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone did not work, provide working phone line 4/2/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 Both jack heads are full of hydraulic oil and getting close to overflowing, clean the drain lines so that the oil can drain into the collection buckets