Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 machine/control room/space illumination is less than 19fc. no lighting in hoistway control space at 2nd floor
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting Machine room illumination is less than 19 fc, no lighting in hoistway control space at 2nd floor
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting Machine/ control room space illumination is less than 19 fc. No lighting in hoistway control space at 2nd floor.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) x Close hoistway penetration, bevel ledges above the hoistway doors, and enclose walls at the top with rated drywall. 7/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Enclose door frames in drywall, door frames are not free standing. 7/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 x Increase illumination in the control space to 19 ft candles minimum, measured from the floor. 7/8/2020
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Replace missing lighting fixture in the pit. Light must be 19 foot candles in illumination 1/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Machine / control room space illumination is less than 19 fc. No lighting in hoistway control space at 2nd floor 10/1/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Smoke detector head is missing on top landing. Replace/reinstall. Reinspection within 10 days. Only unit in building. Did not red tag at this time 5/28/2024