A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
|
|
Replace missing lighting fixture in the pit. Light must be 19 foot candles in illumination
|
1/10/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
|
|
Machine / control room space illumination is less than 19 fc. No lighting in hoistway control space at 2nd floor
|
10/1/2022
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
|
|
machine/control room/space illumination is less than 19fc. no lighting in hoistway control space at 2nd floor
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Machine room illumination is less than 19 fc, no lighting in hoistway control space at 2nd floor
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Machine/ control room space illumination is less than 19 fc. No lighting in hoistway control space at 2nd floor.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Smoke detector head is missing on top landing. Replace/reinstall. Reinspection within 10 days. Only unit in building. Did not red tag at this time
|
5/28/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
x
|
|
Close hoistway penetration, bevel ledges above the hoistway doors, and enclose walls at the top with rated drywall.
|
7/8/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Enclose door frames in drywall, door frames are not free standing.
|
7/8/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
x
|
|
Increase illumination in the control space to 19 ft candles minimum, measured from the floor.
|
7/8/2020
|