Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired. Replace or have serviced 3/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 x Install GFCI receptical in elevator machine room. 6/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.1.1 x Install fire rated door and frame on the elevator machine room. 6/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Install fire extinguisher in machine room. 6/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x Move heat detector to within 24 inches of sprinkler head. 6/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x Label disconnects in the machine room with function and feed location. 6/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x Secure flex in machine room. 6/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) x Seal hoistway penetrations at rear of hoistway. 6/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 8.11.2.1.2(d) x Seal machine room penetrations. 6/3/2020