ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
x
|
|
Increase pit illumination to 10 ft candles measured at the floor.
|
11/12/2020
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in the elevator cab does not work. Re-inspection required
|
3/31/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab is not being answered, needs repair. Re-inspection required
|
4/28/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.1
|
x
|
|
Raise buffers to provide jack clearance.
|
11/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
x
|
|
Increase control space illumination to 19 foot candels measured at the floor.
|
11/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
8.6.4.11
|
x
|
|
Increase top runby to 3" minimum.
|
11/12/2020
|