Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a emergency light/bell battery dead 5/19/2019
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x No active telephone line,no emergency light /alarm 5/5/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Elevator settling approx 1" IN 15 MIN-close machine room valve 8/30/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Check control valve for leackback 8/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate Provide code data plate conforming to sec 8.9 8/30/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 2021 violation for 2.32 not corrected. Repair/replace valve as needed. REINSPECTION REQUIRED WITHIN 30days 5/4/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary battery lowering is not working. needs repaired. Re-inspection required 5/14/2024