MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety / code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch.
|
8/26/2025
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
The elevator control valve seeped an excessive amount of oil in testing. The control valve shall be repaired or replaced
|
8/26/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.5 Code Data Plate
|
|
|
Provide code data plate conforming to sec 8.9
|
8/30/2021
|
|
conversion
|
conversion
|
n/a
|
|
|
emergency light/bell battery dead
|
5/19/2019
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Elevator settling approx 1" IN 15 MIN-close machine room valve
|
8/30/2021
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Check control valve for leackback
|
8/30/2021
|
|
MO Minimum : Elevators
|
(G)2-Alterations
|
8.7.2.14.2 Car Enclosure
|
x
|
|
No active telephone line,no emergency light /alarm
|
5/5/2020
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Auxiliary battery lowering is not working. needs repaired. Re-inspection required
|
5/14/2024
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Auxiliary battery lowering is not working, need repaired. Re-inspection required
|
8/26/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
2021 violation for 2.32 not corrected. Repair/replace valve as needed. REINSPECTION REQUIRED WITHIN 30days
|
5/4/2022
|