MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in cab is not working, needs repaired. Re-inspection required
|
9/10/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
The “Emergency Power” operation failed to activate during emergency power testing, repair system to operate as required. Reinspection required.
|
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5 Gland Packing and Seals
|
x
|
|
Oil is leaking from right jack, overflowing into pit. Repair leak & clean pit.
|
2/24/2022
|