Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.4 - Sills and car floor 8.10.2.2.1(d) Yes No 1st floor landing shall be substantially level with the hoistway door sill. 9/21/2021
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.10.2.2.4(b) Yes No 3rd door hanger and center fire tab is missing on some doors. 9/21/2021
A17.1-2016 : Elevators 3.1 - Top-of-car stop switch 8.10.2.2.3(a) Yes No A stop switch is required near the drive machine. 9/21/2021
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 8.10.2.2.3(bb) Yes No Correct the spacing on rope clips at shackles. 9/21/2021
A17.1-2016 : Elevators 1.3 - Operating control devices 8.10.2.2.1(c) Yes No Secure the re-opening device wire on the front of the cab. 9/21/2021
A17.1-2016 : Elevators 1.12 - Car enclosure 8.10.2.2.1(l) Yes No The interior lower wall panel trim is required. 9/21/2021