ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Install fire extinguisher near the control space.
|
11/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.2 Minimum Illumination
|
x
|
|
Increase machine space illumination to 19 foot candles minimum, measured at the floor.
|
11/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Supply auxiliary contract in control space disconnect to prevent standby power from lowering when disconnect is turned off.
|
11/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
x
|
|
Re-level pit floor to prevent accumulation of water.
|
11/15/2024
|