A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
|
|
All electrical equipment and wiring shall conform with NFPA70. Disconnect wiring shall be put in EMT pipe or greenfield less than 6 ft
|
6/25/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone has to be installed in elevator cab. Re-inspection required
|
3/25/2024
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room door is required to be self closing & self locking
|
6/25/2024
|
A17.1-2016: Residential
|
5.3.1 Private Residence Electric Elevators
|
5.3.1.18.3 Key-Operated Switches
|
|
|
Hall buttons shall be operated by means of a key switch with the key removable only when switch is in the off position. Keyed switched shall not be of continuous pressure spring return type.
|
6/25/2024
|
A17.1-2016: Residential
|
5.3.1 Private Residence Electric Elevators
|
5.3.1.7.1 Hoistway Enclosure Provided
|
|
|
Where requires, landing openings shall be protected by swinging or sliding doors or gates. 1st floor door needs to be replaced.
|
6/25/2024
|
A17.1-2016: Residential
|
5.3.1 Private Residence Electric Elevators
|
5.3.1.7.2 Clearance Between Hoistway Doors and Landing Sills
|
x
|
|
Clearance between the face of the hoistway doors and hoistway edge of the landing sill shall not exceed 9 mm for sliding doors
|
3/25/2024
|
A17.1-2016: Residential
|
5.3.1 Private Residence Electric Elevators
|
5.3.1.8.2 Car Doors and Gates
|
|
|
A car door or gate will guard the opening to the height of at least 66 inches shall be provided at each entrance to the car
|
6/25/2024
|
A17.1-2016: Residential
|
5.3.1 Private Residence Electric Elevators
|
5.3.1.8.3 Clearance Between Hoistway Doors and Car Doors or Gates
|
x
|
x
|
The distance between the hoistway face of the landing door or gate and the car door or gate shall not exceed 100 mm
|
3/25/2024
|