Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.17 - Door and gate equipment 2.11.11.8 Hoistway Door safety retainers missing on both Hoistway entrances
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 x A MCP shall be in place as specified in A17.1 2016 - Sections 8.6.1.2.2 and 8.6.1.4. 9/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x 2.11.11.8 Bottom Hoistway Door Safety Retainers Missing. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail 9/22/2023