A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.10.2.2.1(o)
|
|
|
no in case of fire signage 2.27.9
|
12/7/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
standby power not tested
|
12/7/2021
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
8.10.2.2.1(d)
|
|
|
car floor not installed
|
12/7/2021
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
|
|
not enough working room betweem disconnect an transformer
|
12/7/2021
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.10.2.2.2(hh)
|
x
|
|
only witnessed the weight test for this elevator, they were not ready for final inspection, need to test everything except for the weight test at the final reinspection
|
2/22/2021
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.10.2.2.2(hh)
|
x
|
|
gov pull thru test not done
|
12/7/2021
|
A17.1-2016 : Elevators
|
2.29 - Car and counterweight safeties
|
8.10.2.2.2(ii)
|
x
|
x
|
didnt test safties
|
12/7/2021
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
|
|
hoistway smoke damper not checked
|
12/7/2021
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
fire int. devices not tested
|
12/7/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
2/22/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
2/6/2023
|