Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.10.2.2.2(hh) Yes No only witnessed the weight test for this elevator, they were not ready for final inspection, need to test everything except for the weight test at the final reinspection 2/22/2021
A17.1-2016 : Elevators 1.4 - Sills and car floor 8.10.2.2.1(d) No No car floor not installed 12/7/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No standby power not tested 12/7/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes fire int. devices not tested 12/7/2021
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.10.2.2.1(o) No No no in case of fire signage 2.27.9 12/7/2021
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 No No hoistway smoke damper not checked 12/7/2021
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.10.2.2.2(hh) Yes No gov pull thru test not done 12/7/2021
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.10.2.2.2(ii) Yes Yes didnt test safties 12/7/2021
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) No No not enough working room betweem disconnect an transformer 12/7/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm bell did not work on battery power, mechanic put in new battery and the alarm bell still didn’t work, troubleshoot and repair battery backup system
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting No No Replace lightbulb in spotlight on top landing for the controller space illumination above car #2 entrance, it was not working
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.6 - Governor-rope tension devices 8.11.2.1.5(g) No No Governor rope needs to shortened, tail sheave is about to trip the switch.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 2/22/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State certificate in machine room 2/6/2023