A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
standby power not tested
|
12/7/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
No
|
No
|
Replace lightbulb in spotlight on top landing for the controller space illumination above car #2 entrance, it was not working
|
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current state certificate in machine room
|
2/22/2022
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current State certificate in machine room
|
2/6/2023
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.10.2.2.2(hh)
|
Yes
|
No
|
only witnessed the weight test for this elevator, they were not ready for final inspection, need to test everything except for the weight test at the final reinspection
|
2/22/2021
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
No
|
No
|
not enough working room betweem disconnect an transformer
|
12/7/2021
|
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.10.2.2.1(o)
|
No
|
No
|
no in case of fire signage 2.27.9
|
12/7/2021
|
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
No
|
No
|
hoistway smoke damper not checked
|
12/7/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.6 - Governor-rope tension devices
|
8.11.2.1.5(g)
|
No
|
No
|
Governor rope needs to shortened, tail sheave is about to trip the switch.
|
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.10.2.2.2(hh)
|
Yes
|
No
|
gov pull thru test not done
|
12/7/2021
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
Yes
|
Yes
|
fire int. devices not tested
|
12/7/2021
|
|
A17.1-2016 : Elevators
|
2.29 - Car and counterweight safeties
|
8.10.2.2.2(ii)
|
Yes
|
Yes
|
didnt test safties
|
12/7/2021
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
8.10.2.2.1(d)
|
No
|
No
|
car floor not installed
|
12/7/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Alarm bell did not work on battery power, mechanic put in new battery and the alarm bell still didn’t work, troubleshoot and repair battery backup system
|
|